Research Request – Customised visual alert system for hearing loss

‹ PrevPage 1 of 9 · Source p. 75Next ›
Comments

DOCUMENT 7 FOI 25/26-0555

Research Request – Customised visual alert system for hearing loss

Brief (Lauren Ms22(1)(a)(ii) - irrelevant material ):

s47F - personal privacy The participant is seeking a customised visual alert system for hearing loss. The participant resides in a detached house in Queensland.

  1. Can you please collate the relevant applicable QLD state based legislation, regulations, rules etc applying to domestic fire alarm systems (relevant to the building type of the participant - she resides in a detached house - class 1a)
  2. In response to q 1, can you please summarise the key points of domestic fire alarm requirements for residential houses Queensland. Including, but not limited to the following key details. a. Power source rules (e.g. hard wired only, hard wired after 2017, 10 year lithium battery etc.) b. Type of smoke alarm required (e.g. photoelectric only, ionisation or Photoelectric etc.) c. Minimum number of detectors and required locations (e.g. one per floor, in each bedroom etc.) d. Replacement rules (e.g. all detectors must be replaced after 10 years, can only replace hard wired with hard wired, must replace with hardwired or 10 year lithium battery by 2027 or whenever it is replaced after 2017 etc.)
  3. Can you please collate the following Australian Standards: (no need to summarise at this stage. Based on what I have read in the past, I anticipate the following may be the most relevant ones to have access to for this advice since I am doing a bit more technical digging than I usually have time for. s47F - personal privacy it might be worth having an official copy rather than me using other access I have outside of work) a. AS1603.17-2011 “Warning equipment for people with hearing impairment” b. AS 1670.1:2018 “Fire detection, warning, control and intercom systems - System design, installation and commissioning - Fire” c. AS 1603.11-2018 “Automatic fire detection and alarm systems Visual warning devices”
  4. Can you please contact one or more suppliers of Bellman and Brooks hearing alert systems (e.g. Word of Mouth Technologies) and ask the following: a. On the Bellman and Symfon website they advertise coloured silicone slips that can be purchased to put on the flash receiver. Can these be purchased in Australia. If not available, why not? b. On the Bellman and Symfon website they advertise a signal repeater (code: BE1510), can this be purchased in Australia. If not available, why not? c. Is there an option for a signal repeater/range extender (other than the one BE1510) that can be purchased and used to improve the Radio Frequency signals used by Brooks and Bellman products

R e s e a r c h – c u s t o m i s e d v i s u a l a l e r t s y s t e m f o r h e a r i n g l o s s P a g e | 1 75 of 112

FOI 25/26-0555

d. Are they aware of any common problems with Bellman and/or Brooks products, including, but not limited to: i. Reliability of the radio frequency system used to connect transmitters and receivers/components? ii. Reliability of power sources, either primary and/or backup sources. iii. If so, what are the common solutions that they might suggest for each problem a person might commonly experience? iv. Fragility of the strobe lights (if there used to be an issue, has this changed, if so when) v. Reliability of the bed shaker to alert the person to the triggering of the fire alarm during sleep. vi. Can any receivers be worn or placed for visibility from outdoor and wet areas, if not, any additional comments.

Date June, 2020

Requesters Jane Ss22(1)(a)(ii) - , Shannon As22(1)(a)(ii) -, Lauren Ms22(1)(a)(ii) - irrelevant material

Craig Os22(1)(a)( (Tactical Research Advisor – TAB/AAT) Jane Ss22(1)(a)(ii) - irre (Research Researcher Team Leader)

Contents

  1. Participant’s dwelling ………………………………………………………………………………………………………. 3
  2. Queensland Smoke Alarm Legislation ……………………………………………………………………………….. 3 Existing Dwellings from January 01, 2017………………………………………………………………………………. 3 Replacement and Upgrading ……………………………………………………………………………………………. 3 Location of Alarms ………………………………………………………………………………………………………….. 4 Existing Dwellings from January 01, 2027………………………………………………………………………………. 4
  3. Responses from Word of Mouth Technology ……………………………………………………………………… 4
  4. Responses from Brooks Australia ……………………………………………………………………………………… 7
  5. References …………………………………………………………………………………………………………………….. 9

Please note:

The research and literature reviews collated by our TAB Research Team are not to be shared external to the Branch. These are for internal TAB use only and are intended to assist our advisors with their reasonable and necessary decision-making.

Delegates have access to a wide variety of comprehensive guidance material. If Delegates require further information on access or planning matters they are to call the TAPS line for advice.

R e s e a r c h – c u s t o m i s e d v i s u a l a l e r t s y s t e m f o r h e a r i n g l o s s P a g e | 2 76 of 112

FOI 25/26-0555

The Research Team are unable to ensure that the information listed below provides an accurate & up-to-date snapshot of these matters.

  1. Participant’s dwelling

The Participant resides in a class 1a dwelling defined as a single dwelling being a detached house or one or more attached dwellings, including a row house, terrace house, town house or villa unit. The Queensland domestic smoke alarm legislation applies to Class 1a and Sole Occupancy Units in Class 2 Buildings. [1]

  1. Queensland Smoke Alarm Legislation

Existing Dwellings from January 01, 2017

Source: Queensland Government, Queensland Fire & Emergency Services, For Existing Dwellings, https://www.qfes.qld.gov.au/community-safety/smokealarms/Pages/existing-properties.aspx. Accessed 10 June 2020. [2]

ReplacementandUpgrading

• Existing smoke alarms manufactured more than 10 years ago must be replaced with photoelectric smoke alarms which comply with Australian Standards (AS) 3786-2014.

• Smoke alarms that do not operate when tested must be replaced immediately.

• When replacing smoke alarms, they must be of a photoelectric type which complies with Australian Standard (AS) 3786-2014.

• When being replaced or upgraded they must be interconnected with every other ‘required’ smoke alarm in the dwelling so all activate together.

• Existing hardwired smoke alarms that need replacement, must be replaced with a hardwired photoelectric smoke alarm.

• In existing domestic dwellings, it is possible to have a combination of smoke alarms (240v and battery operated) and interconnectivity can be both wired and/or wireless.

• Legislation for existing dwellings after January 01, 2017 and prior to January 01, 2027, does not indicate an option for alarms to be powered by a non-removable 10-year battery.

R e s e a r c h – c u s t o m i s e d v i s u a l a l e r t s y s t e m f o r h e a r i n g l o s s P a g e | 3 77 of 112

FOI 25/26-0555

LocationofAlarms

Alarms should be placed:

• on each storey • in each bedroom • in hallways that connect bedrooms and the rest of the dwelling • if there is no hallway, between the bedroom and other parts of the storey; and • if there are no bedrooms on a storey, at least one smoke alarm must be installed in the most likely path of travel to exit the dwelling.

Existing Dwellings from January 01, 2027

• All existing private homes, townhouses and units will require photoelectric interconnected smoke alarms.

• Alarms must be either a hardwired (eg. 240v) or non-removable 10 year battery powered type alarm.

• From January 01, 2027 legislation requires smoke alarms must be installed as outlined above for existing dwellings from January 01, 2017.

  1. Responses from Word of Mouth Technology

Below are responses from Andrew Willis at Word of Mouth Technology

R e s e a r c h – c u s t o m i s e d v i s u a l a l e r t s y s t e m f o r h e a r i n g l o s s P a g e | 4 78 of 112

FOI 25/26-0555

a) On the Bellman and Symfon website they advertise coloured silicone slips that can be purchased to put on the flash receiver. Can these be purchased in Australia? If not available, why not? Word of Mouth Technology did have some stock of the silicone covers for the Flash Receiver, however we did not sell one cover in the time that we had them. In our own testing, we found that the covers actually reduced the visibility of the flashing light, with some colours being barely noticeable unless you are directly looking at the receiver (blue in particular). The normal operation of the bright white light and coloured LED is suitable for most clients as you can clearly identify the colours from a distance of a few metres (this allows you to determine which alert is being activated) b) On the Bellman and Symfon website they advertise a signal repeater (code: BE1510), can this be purchased in Australia. If not available, why not? The repeater is not available in Australia as it uses the frequency of 868MHz. This frequency is not permitted to be used in Australia for these devices. It is reserved by the ACMA for other applications. c) Is there an option for a signal repeater/range extender (other than the one BE1510) that can be purchased and used to improve the Radio Frequency signals used by Brooks and Bellman products We can only advise on Bellman products and there is no repeater option. If a client has a specific need we can provide work around solutions – i.e. if they are having issues with coverage of the door transmitter only we can resolve this by using a third party door chime and placing our transmitter in a central position in the house. We don’t have a very high incident of complaints around transmission distance, in most cases when reported it is the users of the push button doorbell transmitter used in a house with brick façade and some internal brick walls or a large home. d) Are they aware of any common problems with Bellman and/or Brooks products, including, but not limited to:

i) Reliability of the radio frequency system used to connect transmitters and receivers/components? Word of Mouth Technology have been distributing Bellman products for 15 years. We have some clients whose products would be over 10 years old and still working, even when new or additional components are purchased. All Bellman devices are backwards compatible with previous products. We believe this makes it a very reliable system.

Transmission range for Bellman Visit products is approximately 40m. This is true for all transmitters except the Bellman Push Button Transmitter, which has a reduced range of approximately 20m. Range is also affected by barriers such as metals or thick walls in client’s homes.

The system operates on a frequency that is approved for such devices. While other equipment uses this frequency the products have specific coding which means interference from external sources is not common. When it does occur we can change the radio key of the product to limit possibility of interference.

This question is sometimes asked by clients, we advise that our system being a closed platform is more stable than some systems that use wifi and rely on third parties allowing their systems to work together. I think there was an issue with this between Google and the Nest products. Some users had found their systems didn’t work anymore because Google and Amazon were not

R e s e a r c h – c u s t o m i s e d v i s u a l a l e r t s y s t e m f o r h e a r i n g l o s s P a g e | 5 79 of 112

FOI 25/26-0555

allowing/sharing their coding. We advise that the Bellman system does not rely on an internet connection, and provides a battery backup for all devices in the instance of a power failure.

I can’t provide comment on the Brooks products, we don’t sell them.

ii) Reliability of power sources, either primary and/or backup sources. All Bellman receivers have a battery back up in them, which allows them to work without connection to mains power. For all products the backup battery is replaceable by the user. The power supplies are rated conservatively, and therefore not subject to a high failure rate. Battery backup in receivers will operate for up to three days in normal use.

We are currently recalling (voluntarily) The Bellman Flash Receiver (BE1442) for units purchased between 2016 and 2019 due to a software fault which relates to the charging of the backup batteries, this fault has been rectified in the current production models. Recalled units are also being fixed by an update to the firmware. There is information about this recall here https://bellman.com/en/for-professionals/be1442-product-recall-overview-page/

iii) If so, what are the common solutions that they might suggest for each problem a person might commonly experience? 1 – If a person requires greater range than the standard doorbell push button BE1250 we suggest a normal doorbell with our BE1023 transmitter.

2 – If a person finds they are getting false alarms we advise them to reset their receiver (we refer them to our YouTube channel which has captioned videos)

3 – False alarms from smoke alarms. Usually because the alarm chamber is contaminated with Dust. We tell the user to clean the alarm or return to us for service if they cannot complete that task.

iv) Fragility of the strobe lights (if there used to be an issue, has this changed, if so when)

The Flash Receiver (BE1442) has a xenon globe that we have found to be very durable over the years. The Bellman Alarm Clocks all use LED technology for strobe alerts, so they are even more long lasting than the xenon globe. There has been no change to the reliability of the strobe in any of our Bellman products over time. We would deem the failure rate of the flash receiver globe/Zenon to be extremely low (less than 1%)

v) Reliability of the bed shaker to alert the person to the triggering of the fire alarm during sleep.

This is quite subjective, and depends on the individual person. We recommend placing the bedshaker between the mattress and the sheet under the pillow area, and this tends to provide good strength vibrations for most people. Some clients prefer to put the bedshaker under the mattress, which can give a reduced vibration, but can still be felt with most mattresses. Alternatively people can place it in the pillowcase, or directly under the pillow, however this could be prone to falling out if the person moves around a lot in their sleep.

In summary the bed shaker is very reliable as it works every time, if a user states they are a heavy sleeper we will always suggest they use our flash receiver or alarm clock with the bed shaker. Lights and vibration are going to increase the reliability of alerting the user.

vi) Can any receivers be worn or placed for visibility from outdoor and wet areas, if not, any additional comments.

R e s e a r c h – c u s t o m i s e d v i s u a l a l e r t s y s t e m f o r h e a r i n g l o s s P a g e | 6 80 of 112

FOI 25/26-0555

Bellman has a Pager Receiver (BE1230) that can be used all over the home. The Bellman Flash Receiver (BE1442) and Bellman Portable Receiver (audible alerts – BE1033) both have battery backup, so can be easily unplugged and moved around the home or outside as needed. With regard to placement in wet areas, the Bellman Visit range has no Ingress Rating, and should be protected from direct contact with water. It would be acceptable to place the receivers in a bathroom on a shelf, or outside if they are protected from the weather.

  1. Responses from Brooks Australia

a) Is there an option for a signal repeater/range extender that can be purchased and used to improve the Radio Frequency signals used by Brooks products

There is a product to extend the range to overcome perceived interference and improve radio frequency performance to EN 300220-3. Part number EIB420RF

b) Are you aware of any common problems with Brooks products, including, but not limited to:

i) Reliability of the radio frequency system used to connect transmitters and receivers/components?

The Brooks radio frequency system is a proprietary radio link using multi-path, multi repeater mesh architecture on the 926 Mhz radiolink protocol which is a very reliable system.

ii) Reliability of power sources, either primary and/or backup sources.

The Brooks alarms are either 240v mains powered and have battery backup or are battery powered only. The products that we have supplied to the deaf and hearing impaired are 10 year lithium battery powered alarms which are guaranteed for life of the alarm.

iii) If so, what are the common solutions that they might suggest for each problem a person might commonly experience?

If the customer maintains the alarms as per guidelines the probability of failure is greatly diminished and is almost non-existent.

iv) Fragility of the strobe lights (if there used to be an issue, has this changed, if so when)

The strobe light fitted with the vibration patrice are plugged into a 240v mains powered product with an SLA battery and is very robust and if maintained will last for the life of the product.

v) Reliability of the bed shaker to alert the person to the triggering of the fire alarm during sleep.

The vibration patrice is an additional pad designed for use with alarms for the hearing impaired and provides additional warning and will activate awakening the occupant.

R e s e a r c h – c u s t o m i s e d v i s u a l a l e r t s y s t e m f o r h e a r i n g l o s s P a g e | 7 81 of 112

FOI 25/26-0555

vi) Can any receivers be worn or placed for visibility from outdoor and wet areas, if not, any additional comments.

R e s e a r c h – c u s t o m i s e d v i s u a l a l e r t s y s t e m f o r h e a r i n g l o s s P a g e | 8 82 of 112

FOI 25/26-0555

All of the Brooks alarms and ancillary products are for indoor use only however your local electrician maybe be able to help with connecting alarms with other Brooks products for visibility from outside.

  1. References

[1] Classification of Buildings and Structures. Queensland Fire & Emergency Services, https://www.qfes.qld.gov.au/community-safety/smokealarms/Documents/QFES-IS- SABuildingClassification.pdf. Accessed 6 Oct. 2020.

[2] Queensland Government, Queensland Fire & Emergency Services, For Existing Dwellings, https://www.qfes.qld.gov.au/community-safety/smokealarms/Pages/existing- properties.aspx. Accessed 10 June 2020. [3] Queensland Government, Queensland Fire & Emergency Services, New dwellings and dwellings being renovated, https://www.qfes.qld.gov.au/community- safety/smokealarms/Pages/new-properties.aspx. Accessed 10 June 2020.

R e s e a r c h – c u s t o m i s e d v i s u a l a l e r t s y s t e m f o r h e a r i n g l o s s P a g e | 9 83 of 112

Comments

Loading comments…

What kind of comment is this?